low pressure water mist nozzle
Model OH-PX2 HC2 / HC3
Min. water pressure
8 bar ≈116 psi
Max. working pressure
16 bar ≈232 psi
Drop size
DV90 < 300 μm
Max distance below ceiling
150 mm
Kv metric
19.0
Flow rate at min pressure
53.7 l/min
Nominal density
4.15 mm/m2
Coverage
3.65 m x 3.65 m
Aesthetic
Aesthetic fire protection
The FIREKILL™ OH nozzles are tested with an open pipework with the distance from the ceiling to the bulb was 150 mm The FIREKILL™ OH nozzles can be delivered in different paint and finishes making the system blend in with almost any type of surface, securing the aesthetics of the surroundings. The nozzles can also be delivered with logo print.
Description
Application
The FIREKILL™ system for protection of non storage applications is unique as it requires very low water pressures and water flow rates. The system utilizes the automatic low-pressure water mist nozzles Model OH-PX2 which are patented pendent automatic, fine water spray nozzles. The OH-PX2 nozzle creates a homogenous fine water mist, which absorbs heat, reduces radiant heat and causes oxygen depletion near the fire, which in turn controls and suppresses the fire. This homogenous mist consists of a high concentration of very small droplets. Because of the small mass of the droplets, the nozzle creates a large coverage, further minimizing the water expenditures and hydrating nearby combustibles.
Test and Approvals
Tested an approved
The FIREKILL™ OH-PX2 has been tested and approved in accordance FM5560:2021 Appendix P Fire Tests for Watermist systems for the protection of non-storage occupancies, Hazard Category 2 (OH-2/HC-2) and Hazard Category 3 (OH-3/HC-3)